ULTRASONIC FLOW METER FOR FUEL GAS CONTROL UX40,UX50,UZ40,AICHI TOKEI VIET NAM AICHI TOKEI Vietnam Đại lý AICHI TOKEI tại Việt nam

Features

No straight pipe section required for installation

It is possible to connect the flow meter directly to a bend such as an elbow piece and a flexible pipe.

As wide as a 1:50 turn down ratio

Applicable also for measuring gas flow of a burner having a large turn down ratio.

Easy to replace batteries

Users can replace batteries without removing the meter from the piping.

Strong against dust, and high durability

Use the product in such a condition that does not allow the gas to re-liquefy into oil mist.

IP64 Protection – available for outdoor use

High temperature can cause the electronic circuit board to be deteriorated and batteries to be consumed. To avoid unnecessary rise in temperature, the product is recommended to be fitted with a sunshade.

Specifications

Model UX40 UX50 UZ40 UZ50
Pipe connection Screw Flange
Rc1・1/2 (40A) Rc2 (50A) JIS10K 40A Flange (1・1/2″) JIS10K 50A Flange (2″)
Maximum working pressure 100kPa 500kPa
Gas type ※1 City gas (13A), butane (butane = 70%, propane = 30%), propane (propane = 98%, butane 2%), nitrogen and argon
Power/
consumption
Battery ※2 Exclusive lithium battery (life = 5 years @20℃ and 65%RH)
AC power 100VAC±15%/max 10W (for 22mA)
DC power 24VDC±10%/max 2W (for 26.4V and 22mA)
Flow range
(Actual flow)
City gas, nitrogen and argon 1.6~80m³/h 3~150m³/h 1.6~80m³/h 3~150m³/h
Butane and propane 3~80m³/h 3~80m³/h
Accuracy ※3 ±4%RD (for a range of 10% to 100% of the max flow)
±0.5%FS (for a range of 2% to 10% of the max flow)
uz40-50_accuracy_w660
Temperature and pressure compensation ※4 Yes/No (Normal/Standard conversion)
Conversion accuracy ±1.5%RD(@23℃ and 100kPa) ±1.5%RD(@23℃ and 500kPa)
Display Main display Accumulated flow (actual flow: 8-digit integer + 2 decimal places, converted flow: 8-digit integer + one decimal place, accumulated flow of trip function)
Alarm indication (for ultrasonic sensor, temperature sensor, pressure sensor, external memory and power voltage (for battery operation only))
Sub display Instantaneous flow: 5 digits; temperature: 3 digits; and pressure: 5 digits
Output Analogue (For 100VAC or 24VDC only) 4-20mADC (load resistance = max 400Ω): choose among options of instantaneous flow, temperature and pressure (default = instantaneous flow)
Pulse Nch open-drain output (maximum load 24VDC, 50mA)
Output 1 (accumulated flow volume pulse): standard = 1000L/P (choose 10, 100, 1000 or 10000 L/P): duty = 20 – 80%
Output 2 (alarms): upper & lower limits, or upper limits of accumulated flow (for 100VAC or 24VDC drive); low voltage, or upper & lower limits (for battery drive)
Communication ※5 (For 100VAC or 24VDC drive) RS485 Modbus/RTU (4800/9600 bps)
Fluid temperature -10℃ to +60℃, under unfrozen condition
Ambient working temperature and humidity -10℃ to +60℃, max 90%RH, no condensation permissible
Protective structure Indoor and outdoor use *6, IP64 (JIS C 0920)
Mass Approximate 4.7kg Approximate 6.3kg Approximate 7.0kg Approximate 8.8kg

*1 Gas type (composition) can be changed on site among those specified here with little degradation in measuring accuracy.
*2 Replaceable without removing the meter from the piping
*3 In case a distance from an elbow of minimum 10D in the upstream side and 5D in the downstream side of the meter can be secured: ±2%RD (for a range of 10% to 100% of the max. flow) and ±0.5%FS (for a range of 2% to 10% of the max. flow).
The distance to a governor should be greater than 10D for both the upstream and downstream sides of the meter. Failing to meet this condition may lead to inaccurate measurements. For other conditions for installation, please contact us.
*4 Normal flow: Conversion of measurement into a flow at 0℃ and 1atm. Standard flow:  Conversion of measurement into a flow at the reference temperature and 1atm
*5 For communication specifications, see our company’s website to download it.
*6 High temperatures can cause the electronic circuit board to be deteriorated and the batteries to be consumed. To avoid unnecessary rise in temperature, the product is recommended to be fitted with a sunshade.

External dimension - UX

Model L H W h Connection diameter
UX40 170 212 118 157 Rc1・1/2 (40A)
UX50 200 227 123 165 Rc2 (50A)

 

ux40-50_dim

External dimension - UZ

Model L H h Connection diameter
UZ40 200 222 157 JIS10K 40A Flange (1・1/2″)
UZ50 220 238 165 JIS10K 50A Flange (2″)